BRONKHORST®
Bronkhorst offers special begin‐termination connectors with the resistor network. This handles correct termination
butalsogivesadefinedvoltageontheRS485‐Aand‐Blineforevenmorereliabilityofthebussystem.
Anend‐terminatorisalsoofferedbyBronkhorstandhandlescorrectterminationadtheendofthebus.
Terminationca
nbeperformedwithspecialtermination‐connectors,offeredbyBronkhorst.
Terminationschematic
RJ45 M12
703297‐‐RJ45Begin
terminator
703298‐‐RJ45End
terminator
Beginterminator Endterminator
FLOW‐BUSsystem
Page16
FLOW‐BUSinterface9.17.024
Atthe beginningof each FLOW‐BUSsystem there always mustbe aresistor network as showed above.This begin‐
terminatorneedstobepartofyoursystem.Bronkhorstoffersspecialbegin‐terminationconnectorswiththeresistor
network.ThishandlescorrectterminationbutalsogivesadefinedvoltageontheRS485‐Aan
d‐Blineforevenmore
reliabilityoftheFLOW‐BUSsystem.
Bronkhorstadvisesalwaystouseaterminationresistorattheendofthebusinyoursystem.Thisend‐terminatoris
alsoofferedbyBronkhorstandhandlescorrectterminationfortheFLOW‐BUS.
+15…24Vdc
RB1
976Ohm
RS485‐A
RT1
12
1Ohm
RB2
392Ohm
RS485‐B
RT2
12
1Ohm
Begintermination(RED) Endtermination(BLACK)