Parameter properties table
Parameter
number
(DDE)
Parameter
name
Group
0
Group
1
Group
2
Process
number
FB
nr
(par)
Var
Type
Var
Length
Min
value
Max
value
Read Write Poll Secured Highly
Secured
Default Value Description
2011-05-18 Page 1 of 5FlowDDE database version V3.64
DDE str
1 Identification string 13 0 0 c -2 Yes Yes No No No 7SN999999 identnr.+softwareversion[+serialnr.]identstrng
2 Primary node address 1 0 1 c 0 128 Yes Yes No Yes Yes 0 primary node address: network parameter FLOW-BUSpna
3 Secondary node address 1 0 2 c 0 128 Yes Yes No Yes Yes 0 secundary node address: network parameter FLOW-BUSsna
4 Next node address 1 0 3 c 0 128 Yes Yes No No No 1 next node address: network parameter FLOW-BUSnna
5 Last node address 1 0 4 c 0 128 Yes Yes No No No 32 last node address: network parameter FLOW-BUSlna
6 Arbitrage 1 0 5 c 0 255 Yes Yes No Yes Yes 67 FLOW-BUS arbitrage setting and/or automatic optimizationarbitrage
7 Initreset 12 0 10 c 0 255 Yes Yes No No No init and reset security key commands for network/parameter settingsinitreset
8 Measure 2 0 i -23593 41942 Yes Yes Yes No No 0 measured value (100% = 32000)measure
9 Setpoint 2 18 1 i 0 32767 Yes Yes Yes No No 0 setpoint: wanted value (100% = 32000)setpoint
10 Setpoint slope 18 2 i 0 30000 Yes Yes No No No 0 setpoint ramp signal 0..100 % in up to slope x 0.1 sec.setpslope
11 Analog input 2 18 3 i -23593 41942 Yes No Yes No No 0 analog input signal, normally used for ext. setp. (100% = 32000)analoginp
12 Control mode 18 4 c 0 255 Yes Yes No No No 0 control mode selection for instrument or modulecntrlmode
13 Polynomial constant A 3 5 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 0.0 polynomial constant A (offset)polycnst A
14 Polynomial constant B 3 6 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 1.0 polynomial constant B (span]polycnst B
15 Polynomial constant C 3 7 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 0.0 polynomial constant Cpolycnst C
16 Polynomial constant D 3 8 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 0.0 polynomial constant Dpolycnst D
17 Polynomial constant E 3 9 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 0.0 polynomial constant E (offset) for setpoint or power valuepolycnst E
18 Polynomial constant F 3 10 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 1.0 polynomial constant F (span) for setpoint or power valuepolycnst F
19 Polynomial constant G 3 11 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 0.0 polynomial constant G for setpoint or power valuepolycnst G
20 Polynomial constant H 3 12 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 0.0 polynomial constant H for setpoint or power valuepolycnst H
21 Capacity 3 19 13 f -3.40282E+38 3.40282E+38 Yes Yes No Yes No 1.0 readout value at 100% in capacity (readout) unitcapacity
22 Sensor type 3 14 c 0 255 Yes Yes No Yes No 3 sensor type information for actual reading and sensor/controller indicationsensortype
23 Capacity unit index 3 19 15 c 0 255 Yes Yes No Yes No 0 pointer to capacity (readout) unit (classic unit table]capunit
24 Fluid number 3 16 c 0 8 Yes Yes No No No 0 fluid number: pointer to fluidset (for e.g. polynome, name and cap.)fluidnr
25 Fluid name 3 17 c 10 Yes Yes No Yes No AIR name of fluidfluidname
26 Claim node 12 18 c 0 128 Yes Yes No Yes No 0 node address of module with operation rightsclaimnode
27 Modify 12 19 c 0 255 Yes Yes No No No 0 contains number(s) of changed par (0xXX par nr, 0xFF more than one par changed)modify
28 Alarm info 4 20 c 0 255 Yes No Yes No No 0 status information of several alarms/errors in the instrumentalarminfo
29 Channel amount 17 0 12 c 1 120 Yes Yes No No No 32 amount of channels which can be operatedchanamount
30 First channel 17 0 13 c 1 120 Yes Yes No No No 1 first channel that can be operatedfirstchan
31 Last channel 17 0 14 c 1 120 Yes Yes No No No 32 last channel that can be operatedlastchan
32 <hostcontrl> 5 9 1 c 0 1 Yes Yes No No No 0 operation by HOST computer enable flaghostcontrl
33 Alarm message unit type 5 10 0 c 16 Yes No Yes No No alarm message string with unit type informationalrmmsgTA
34 Alarm message number 5 10 1 c 16 Yes No Yes No No alarm message string with unit number informationalrmmsgnr
35 Relay status 5 10 2 c 8 Yes No No No No status of relays/potential free contacts ('0' = not activated, '1' = activated)relstatus
36 Actual counter value 5 0 f 0 3.40282E+38 Yes No Yes No No 0 actual value of counteractualval
37 Signal input selection 5 1 c 8 Yes Yes No No No signal input selection (' '=no value,'+'=pos value,'-'=neg value input)signinpsel
38 Reset input selection 5 2 c 8 Yes Yes No No No external reset input enable/disable ('E'=enable,' '=disable)resinpsel
39 <limit> 5 3 f 0 3.40282E+38 Yes Yes No No No limit/batch for counter in sensor standard unitslimit
40 Delay time 5 4 c 8 0 99235959 Yes Yes No No No 00000000 delay time string in days,hours,minutes,secondsdelaytime
41 Duration time 5 5 c 8 0 99235959 Yes Yes No No No 00000000 duration time string in days,hours,minutes,secondsduratntime
42 Valve output setting 5 6 c 8 Yes Yes No No No 00000000 valve output setting ('0'=do nothing, '1'=close valve)vlvoutset
43 Relay output setting 5 7 c 8 Yes Yes No No No LLLLLLLL relay output setting ('L'=low, 'H'=high, 'P'=pulse (1 sec.))reloutset
44 Operation mode T/A 5 8 c 0 9 Yes Yes No No No 0 operation mode of T/A moduleopermodeTA
45 Readout unit 5 9 c 7 Yes No No No No ln/min readout unit stringreadunit
46 Readout factor 5 10 f 1E-10 10000000000 Yes No No No No 1 readout factor matching readout unit stringreadfact
47 Reset unit 5 12 c 0 1 No Yes No No No reset unit command (1=reset T/A unit)resetunit
48 Valve differentiator down 6 9 f 0 3.40282E+38 Yes Yes No Yes No 0.1 valve output differentiation time constant downwardsTdValveDn
49 Valve differentiator up 6 10 f 0 3.40282E+38 Yes Yes No Yes No 0.1 valve output differentiation time constant upwardsTdValveUp
50 Sensor differentiator down 6 11 f 0 3.40282E+38 Yes Yes No Yes No 5.8 sensor signal differentiation time constant downwardsTdSensorDn
51 Sensor differentiator up 6 12 f 0 3.40282E+38 Yes Yes No Yes No 5.6 sensor signal differentiation time constant upwardsTdSensorUp
52 Cycle time 6 114 12 c 0 255 Yes Yes No Yes No 6 cycle time * 10 msec. main loop signal processingCycleTime
53 Analog mode 10 115 3 c 0 255 Yes Yes No Yes No 0 analog mode selection for analog operationAnalogMode
54 Reference voltage 10 116 6 i 0 65535 Yes Yes No Yes No reference voltage output signal for analog operationVrefOutput
55 Valve output 8 114 1 l 0 16777215 Yes Yes Yes No No 0 valve output signal (24-bit number in range 0..14.3Vdc/0..23.3Vdc)ValveOut
56 Dynamic display factor 6 117 1 f 0 1 Yes Yes No Yes No 0,001 dynamic display factor for display filter (0=max, 1=min goes with par 57)DynDispFct
57 Static display factor 6 117 2 f 0 1 Yes Yes No Yes No 0,000001 static display factor for display filter (0=max, 1=min goes with par 56)StaDispFct
58 Calibration mode 7 115 1 c 0 255 Yes Yes No Yes No 0 calibration mode selection (not active until cntrlmode has been set to value 9)CalMode
59 Valve offset 8 116 7 i -32767 65535 Yes Yes No Yes No 61000 valve offset: amount of DAC steps within 1 potmeter stepValveOffst
60 Monitor mode 2 115 2 c 0 255 Yes Yes No Yes No 7 monitor: output signal (measure) selection for bus and analog outputMonitor
61 Alarm register1 4 114 2 c 8 Yes Yes No Yes No alarm register containing warning flagsAlarmReg1
62 Alarm register2 4 114 3 c 8 Yes Yes No Yes No alarm register containing critical error flagsAlarmReg2
63 <CalRegZS1> 9 116 1 l 0 16777215 Yes Yes No Yes No 210A7D calibration register zero scale input 1 ADCCalRegZS1
64 <CalRegFS1> 9 116 2 l 0 16777215 Yes Yes No Yes No 52A513 calibration register full scale input 1 ADCCalRegFS1
65 <CalRegZS2> 9 116 3 l 0 16777215 Yes Yes No Yes No 210A7D calibration register zero scale input 2 ADCCalRegZS2
Vue de la page 38
1 2 ... 34 35 36 37 38 39 40 41 42 43

Commentaires sur ces manuels

Pas de commentaire

Silvercrest Timer Switches DIGITAL Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Für Zuhause Silvercrest Timer Switches DIGITAL.
Wir stellen 3 PDF-Handbücher Silvercrest Timer Switches DIGITAL zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Bedienungsanleitung






Weitere Produkte und Handbücher für Für Zuhause Silvercrest

Modelle Dokumententyp
Timer Switches MECHANISCH Bedienungsanleitung     Silvercrest Timer Switches MECHANISCH User Manual, 2 Seiten
SFK 36 A1 Bedienungsanleitung   Silvercrest SFK 36 A1 User Manual, 44 Seiten
SFK 36 A1 Bedienungsanleitung    Silvercrest SFK 36 A1 Manual del usuario, 44 Seiten
SFK 36 A1 Bedienungsanleitung    Silvercrest SFK 36 A1 Benutzerhandbuch, 44 Seiten
SFK 36 A1 Bedienungsanleitung     Silvercrest SFK 36 A1 User Manual, 44 Seiten
Z31370A Z31370B Bedienungsanleitung     Silvercrest Z31370A Z31370B Benutzerhandbuch, 58 Seiten
Z31370A Z31370B Bedienungsanleitung    Silvercrest Z31370A Z31370B Benutzerhandbuch, 69 Seiten
Z31370A Z31370B Bedienungsanleitung    Silvercrest Z31370A Z31370B Benutzerhandbuch, 33 Seiten
Z31370A Z31370B Bedienungsanleitung      Silvercrest Z31370A Z31370B User Manual, 83 Seiten
Z31370A/Z31370B Bedienungsanleitung    Silvercrest Z31370A/Z31370B Benutzerhandbuch, 35 Seiten
Z31370A/Z31370B Bedienungsanleitung      Silvercrest Z31370A/Z31370B User Manual, 100 Seiten
SDR 900 A1 Bedienungsanleitung    Silvercrest SDR 900 A1 Benutzerhandbuch, 54 Seiten
SDR 900 A1 Bedienungsanleitung      Silvercrest SDR 900 A1 User Manual, 84 Seiten
SDR 900 A1 Bedienungsanleitung      Silvercrest SDR 900 A1 User Manual, 116 Seiten
SFR 3.7 A2 Bedienungsanleitung      Silvercrest SFR 3.7 A2 User Manual, 44 Seiten
SFR 3.7 A2 Bedienungsanleitung      Silvercrest SFR 3.7 A2 User Manual, 54 Seiten
SFR 3.7 A2 Bedienungsanleitung      Silvercrest SFR 3.7 A2 User Manual, 74 Seiten
SFK 16 A1 Bedienungsanleitung    Silvercrest SFK 16 A1 Benutzerhandbuch, 81 Seiten
SFK 16 A1 Bedienungsanleitung     Silvercrest SFK 16 A1 User Manual, 155 Seiten
Z30914 Bedienungsanleitung     Silvercrest Z30914 Benutzerhandbuch, 63 Seiten