BRONKHORST®
Page18RS232interface 9.17.027
Answerto therequest
Nr Byte Layout Description
0 :
startcharacter
1 Length
Messagelength
2 Node
Nodeaddress
3 02
Commandwrite
4* Process cppppppp
c Processchained
p Processnumber
5* Parameter cttnnnnn
c Parameterchained
t Parametertype
n Parameterindex0…31
6 Value1
Valueforalltypes.For‘strings’thisfieldcontainsthestringlength.
7 Value2
Valuefortype‘integer’,‘float’or‘long’.
8 Value3
Valuefortype‘float’or‘long’.
9 Value4
Valuefortype‘float’or‘long’.
X Valuex
Morevaluefieldsfollowfortype‘string’dependingonstringlength.Ifgiven
stringlengthiszero,thefinalfieldshouldalsocontainazero.
X+1 \r
CarriageReturn
X+2 \n
LineFeed
*Therequestedmodulecopiesthesevaluesfromtherequestmessagedirectlyintotheanswer
message.