4 OBJECTDESCRIPTION
4.1 SUPERVISOROBJECT
4.1.1 FLOWBUSinterfacing(viaRS232)
ToenablecontrollingthedevicebyRS232,anewcontrolmodehasbeenadded:CTRL_RS232(18).Thiscontrolmode
isequalto CTRL_FB (0), butinthiscase thedevice will always makethetransitionto theEXECUTINGstate(nostart
request or receipt of I/O data needed). So CTRL_RS232
makes it possible to give setpoints without the need of a
DeviceNetconnection.
ThedevicewillonlybecompliantwiththeODVAprofilewhencontrolmodeisCTRL_FB(0).
In case of taking over control via RS232, it is possible to send value 18 to parameter “Control Mode” (FLOWBUS:
proc1, par4 or FLOWDDE: parameter 12). From this moment on, it will be possible to give setpoints without being
overruledbythesafestate.Thiscontrolmodewillbevaliduntilthenextpowerupsituation.Controlmode=18will
notbestoredintononvolatilememory.Ateachpower
up,theinstrumentwillbenormallysettocontrolmode=0.
ThesafestateisactivewhenthedeviceisnotintheEXECUTINGstate.
ThefunctionalityoftheRS232FLOWBUS“ControlMode”parameterisnotthesameastheControl
ModeattributeintheSingleStateControllerObject(attribute0x05,object0x33).
4.1.2 I/Oassemblyinstancesselection
Attribute0x66and0x67canbeusedtoselecttheI/OassemblyinstancesusedforthePolledI/Oconnection(seealso
PolledI/Oinput/outputparametersinEDSfile).
Devicenet InputI/Oassembly
obj0x30,attr102 instance
0 2
1 6
2 14
3 18
Devicenet OutputI/Oassembly
obj0x30,attr103 instance
0 7
1 8
2 19
3 20