12.1.3 DeviceNeterrordescription
SITUATION Description
Minorcommunicationerror
(redLED:0.1secon,2secoff)
Eachcommunicationerrorwillbeseenasaminorcommunicationerror
exceptforwhentheinstrumentisinthecommunicationfaultstate.
Instrumentwillstayintheon‐linestate.Theseerrorswillberecovered
automatically.
Examplesofminorerrors:
WheninstrumentisonlymemberonDeviceNetnetwork
WhenanI/Oconnectiontime‐outhasoccurred
Nobuspower
(redLED:0.2secon,0.2secoff)
Instrumenthardwaredetectsthat+24VdcinDeviceNetcableisnotpresent.
Seriouscommunicationerror
(redLED:2secon,0.1secoff)
Instrumentwillget incommunicationfaultstate.Thiswillhappenat
duplicateMACIDoratbus‐offevent(Thisnodeisfaultyandisnotallowedto
haveanyinfluenceonthebus).Thisstatecanonlybe
leftbymanual
intervention.Instrumentneedsareseteitherbyusingthemicro‐switchon
topoftheinstrumentoranewpower‐up.AtduplicateMACIDsituation,
sendinganewMACIDviaRS232(e.gusingFlowFix)couldalsosolvethe
problem.
12.2 TROUBLESHOOTINGHINTSANDTIPS
SITUATION Description
DeviceNetproblems CheckallDeviceNetsettingsatyourmaster.Masteranddevicesettingsfor
useofmemorymodulesmustbethesame.Makesureselected
configurationatdeviceconfigurationforpolledI/Oisthesameasthe
settingsatparameterdata.Seechapter7formoredetails.
CheckMACIDand
Baudrateofdevice(slave).
CheckcablingandbusterminationofyourDeviceNetsystem.
Checkpowersupply.Instrumentsneed+24Vdc.
Trytoresettheinstrumentand/orrestartyourmaster.
Makesureallsettingsforyourslavearedownloadedtoyourmaster
(otherwiseitwon’twork).
ContactDeviceNetsales
representativeorservicedepartment.
Other(FLOW‐BUS)problems ContactBronkhorst localsalesrepresentativeorsende‐maildescribingyour
problemto:seeservicechapter.